1. Find your amps
Your sanctioned load is on the NBPDCL bill, in kW. Multiply by 1,000 and divide by 230.
The MCB protects the wire. Pick its amps from the wire, and its letter from the load.
Add a 30 mA RCCB after the main: it is the only thing on the board that switches off when current leaks through a person.
Read across. The wire column decides the amps; the load decides B or C. How many amps each wire size carries, with worked examples, is on the wire amps chart. This page is about the MCB.
| Circuit | Wire | MCB | Why |
|---|---|---|---|
| Lights and fansone circuit per floor | 1.5 sq mmor 1 sq mm | B10B6 on 1 sq mm | No motor surge worth the name. 1.5 sq mm carries 13 A in a pipe, 1 sq mm 11 A. |
| 6 A socketsTV, chargers, lamps | 1.5 sq mm | B10 | If a cooler or mixer will plug in here, make it C10. |
| Kitchenmixer, fridge, microwave, induction | 2.5 sq mm | C16 | Mixer and fridge are motors. Its own line, not shared with a room. |
| 16 A socketsiron, washing machine, heater | 2.5 sq mm | C16 | Washing machine starts a motor. 6 A vs 16 A sockets. |
| Geyserup to 3 kW | 2.5 sq mm | 16 A DPB or C | 2 kW is about 9 A, 3 kW about 13 A. Double pole, taking two ways. No motor, so either letter. Above 3 kW, send us the plate. |
| AC, plate up to 12 Amost 1 and 1.5 ton splits | 2.5 sq mm | C16 | One AC, one MCB. Compressor start needs C. Wire for an AC. |
| AC, plate 12–16 A | 4 sq mm | C20 | 4 sq mm carries 24 A in a pipe, so 20 A fits. Above 16 A, send us the plate. |
| Water pumpown line | by plate | C16 / C20 | Same plate rule as the AC: up to 12 A on 2.5 sq mm with C16, 12–16 A on 4 sq mm with C20. Wire for a pump. |
| Main | 4 or 6 sq mm | DP 20 / 25 | Double pole, sized to the sanctioned load and the main wire. Below. |
| RCCB | after the main | 30 mA DP | Amps equal to or above the main. Below. |
A B16 and a C16 both carry 16 A all day. The letter sets how big a sudden surge the MCB lets pass before it snaps off. V-Guard's Elegna sheet gives the bands.
Trips at once at 3 to 5 times its rating. Quicker on a short in a thin light wire, and nothing on these circuits starts with a big surge.
Waits until 5 to 10 times its rating. AC compressor, fridge, pump, mixer and washing machine pull a burst as they start; a B-curve reads it as a fault and drops.
A heating element has no start surge, so B or C both work. The piece for a geyser is 16 A double-pole, as CPWD's wiring specification recommends for water heaters, and it takes two ways on the board.
D-curve is for heavy factory motors, not houses. If a correct C-curve still trips as a motor starts, the motor is the problem, not the MCB: MCB tripping again and again. The full B vs C story: B curve vs C curve MCB.
Circuit MCBs are single pole (SP): they cut the phase. The geyser's is double pole, like the main. The main is double pole (DP): it cuts phase and neutral together, so the house is fully dead when you switch it off. More in SP vs DP MCB.
Your sanctioned load is on the NBPDCL bill, in kW. Multiply by 1,000 and divide by 230.
The main can't be bigger than the wire from the meter carries in its pipe: 4 sq mm 24 A, 6 sq mm 31 A.
| Sanctioned load | Main MCB | Main wire |
|---|---|---|
| up to 4.6 kWup to 20 A | DP 20 A | 4 sq mm at least; 6 sq mm if you will add an AC later |
| 4.6 to 5.75 kW20 to 25 A | DP 25 A | 6 sq mm |
| above 5.75 kWover 25 A | send us the load | Needs a heavier main or a three-phase connection |
No. That is normal. A board might hold B10 + B10 + C16 + 16 A DP + C16 + C20 + C16 = 104 A of MCBs, but they never all run full at once: the lights don't draw 10 A, the geyser runs twenty minutes. The main is sized to what the house really draws together, which is what the sanctioned load is meant to cover.
An MCB only feels big currents: an overload or a short. A leak through someone's hand is far too small for it to notice. An RCCB compares what goes out on the phase with what comes back on the neutral, and switches off when the difference is 30 mA.
The order on the rail is the order in the drawing at the top: main, RCCB, then one SP MCB per circuit (a DP for the geyser). How you split the circuits matters more than the order.
Most of these work for months. They show up on the first night of real load, or the day someone gets a shock.
Between 18 and 20 A the wire runs hot in the wall and nothing trips. Use 16 A on 2.5, or run 4 sq mm for 20 A.
1.5 sq mm carries 13 A in a pipe. Its MCB is B10. A 16 A there protects nothing.
A big MCB to stop that tripping leaves every thin wire on it unprotected. Split the circuits: one MCB per heavy load.
Same amps, letter C. Don't go up in amps to stop it.
An SP MCB must sit in the phase (red). If it is in the neutral, the light goes off but the wire stays live.
The RCCB must be rated at or above the main. Press T once a month; if it doesn't drop, replace it.
Tell us what the house has. You get every MCB with its letter and wire, the main, the RCCB and the number of ways for the DB box. Read your AC and pump plates for their amps.
Rules: wire limits from V-Guard Classo+ (Finolex for 6 sq mm), MCB curves from the Elegna sheet, RCCB ratings from V-Guard's Invidia sheet. Prices Ask rate each, filled in from today's rate. Wire metres for the whole house: wiring calculator.
Prices are from our latest bill and change often. Please confirm today's rate on WhatsApp or call before buying.
Elegna 10 A, B-curve, SPLights, fans, 6 A sockets on 1.5 sq mm · on the shelf₹ 121per piece Elegna 20 A, C-curve, SPAC or pump on 4 sq mm only · on the shelfAsk today's rateper piece Elegna 16 A, C-curve, SPKitchen, AC up to 12 A on 2.5 sq mm · ordered for youAsk today's rateper piece Elegna 16 A, double poleOne per geyser, on 2.5 sq mm · ordered for youAsk today's rateper piece Elegna DP main, 20 or 25 ADouble pole · and B6, B16, any rating 6–63 A · ordered for youAsk today's rateper piece V-Guard RCCB, 30 mA DPInvidia range, 25 A for a 20/25 A main · ordered for youAsk today's rateper piece DB boxThe ways the builder counts · ordered for youAsk today's rateper pieceAnything not on the shelf, we order for you; ask on WhatsApp for the time it takes. Every piece comes on a GST bill with the box QR you can check on V-Guard's site (asli ya nakli MCB). Today's prices: electrical rates.
Go by the current on the AC's name plate. Up to 12 A, which is most 1 and 1.5 ton splits: 2.5 sq mm wire and a 16 A C-curve MCB. From 12 to 16 A: 4 sq mm wire and a 20 A C-curve MCB. Above 16 A, send us the plate. Every AC gets its own MCB. Details: wire for an AC.
A 2 kW geyser draws about 9 A and a 3 kW one about 13 A, so both go on 2.5 sq mm wire with a 16 A double-pole MCB, B or C curve; CPWD's wiring specification (Part I, 2013, cl. 3.14) recommends double-pole protection for water heaters, and a DP takes two ways on the board. Not 20 A: 2.5 sq mm in a wall pipe carries 18 A (V-Guard Classo+).
16 A. V-Guard rates Classo+ 2.5 sq mm at 18 A inside a pipe, so a 20 A MCB would let the wire run hot without tripping. A 20 A MCB goes only on 4 sq mm, which carries 24 A in a pipe.
A 10 A B-curve MCB on 1.5 sq mm wire, or a 6 A B-curve on 1 sq mm. Never 16 A on 1.5 sq mm, which carries only 13 A in a pipe.
A double-pole (DP) MCB. It must be at least your sanctioned load in amps (kW × 1,000 ÷ 230) and no bigger than the main wire carries: up to DP 20 A on 4 sq mm, up to DP 25 A on 6 sq mm in a pipe. Above about 5.75 kW, send us the load: it needs a heavier main or a three-phase connection.
Yes. Regulation 44 of the Central Electricity Authority (Measures relating to Safety and Electric Supply) Regulations, 2023 requires a residual current device of not more than 30 mA in a domestic installation. An MCB protects the wire from overload and short circuit; it does not feel a small leak through a person. A 30 mA double-pole RCCB, fitted after the main, switches off when current leaks to earth. Its rating should be equal to or above the main MCB.
B for lights, fans and plain sockets. C for anything with a motor or compressor: AC, fridge, kitchen, washing machine and water pump. The curve never changes the amps; those come from the wire.
Usually: B10 lights and fans, B10 6 A sockets, C16 16 A sockets, C16 kitchen, 16 A double-pole geyser, C16 for each AC, C16 for the pump: about 6 SP MCBs and one DP for the geyser, plus the DP main and an RCCB. Put your own house into the builder above.
No. A bigger MCB stops the tripping by letting the wire overheat. Find the cause: MCB tripping again and again.