Which MCB for which load? Lights, sockets, AC, geyser, motor and the main

The short answer

The MCB protects the wire. Pick its amps from the wire, and its letter from the load.

  • B10Lights and fans, 6 A sockets · 1.5 sq mm (B6 on 1 sq mm)
  • C16Kitchen, 16 A sockets · 2.5 sq mm. Never 20 A on 2.5.
  • 16 DPGeyser · 2.5 sq mm, double pole, takes two ways on the board
  • C16AC or pump, plate up to 12 A · 2.5 sq mm, its own line
  • C20AC or pump, plate 12–16 A · 4 sq mm, its own line
  • DPMain · at least your sanctioned load, no more than the main wire carries

Add a 30 mA RCCB after the main: it is the only thing on the board that switches off when current leaks through a person.

18 A
2.5 sq mm in a wall pipeV-Guard Classo+. So 16 A on it, not 20 A.
B / C
The letterC lets a motor start without tripping. B for everything else.
÷ 230
Watts to ampsA 2,000 W geyser is about 9 A.
A house board, in the order power flows
A distribution board for a two-floor house Power comes from the meter on 6 sq mm wire into a 25 A double-pole main, then a 30 mA RCCB, then a row of MCBs, single-pole except the geyser's: B10 for lights and fans on 1.5 sq mm, B10 for 6 A sockets, C16 for the kitchen on 2.5 sq mm, a 16 A double-pole for the geyser on 2.5 sq mm, C16 for an AC up to 12 A on 2.5 sq mm, C20 for an AC from 12 to 16 A on 4 sq mm, C16 for the pump on 2.5 sq mm, and one spare. from meter · 6 sq mm L N DP 25 30 mA T 1 · MAIN cuts phase + neutral 2 · RCCB 25 A trips on leakage 3 · ONE MCB PER CIRCUIT, IN THE PHASE WIRE B10 B10 C16 16 DP C16 C20 C16 SPARE Lights, fans6 A socketsKitchenGeyser AC ≤ 12 AAC 12–16 APumpfor later 1.5 sq mm1.5 sq mm2.5 sq mm2.5 sq mm 2.5 sq mm4 sq mm2.5 sq mm
Drawn for a two-floor house. Real boards sit in one row; the lights, fans and sockets repeat once per floor. Neutrals go to the neutral bar and green wires to the earth bar, never through an MCB. MCB figures: V-Guard Elegna; wire figures: V-Guard Classo+.
The full chart

Every circuit in a house: wire, MCB and letter

Read across. The wire column decides the amps; the load decides B or C. How many amps each wire size carries, with worked examples, is on the wire amps chart. This page is about the MCB.

CircuitWireMCBWhy
Lights and fansone circuit per floor1.5 sq mmor 1 sq mmB10B6 on 1 sq mmNo motor surge worth the name. 1.5 sq mm carries 13 A in a pipe, 1 sq mm 11 A.
6 A socketsTV, chargers, lamps1.5 sq mmB10If a cooler or mixer will plug in here, make it C10.
Kitchenmixer, fridge, microwave, induction2.5 sq mmC16Mixer and fridge are motors. Its own line, not shared with a room.
16 A socketsiron, washing machine, heater2.5 sq mmC16Washing machine starts a motor. 6 A vs 16 A sockets.
Geyserup to 3 kW2.5 sq mm16 A DPB or C2 kW is about 9 A, 3 kW about 13 A. Double pole, taking two ways. No motor, so either letter. Above 3 kW, send us the plate.
AC, plate up to 12 Amost 1 and 1.5 ton splits2.5 sq mmC16One AC, one MCB. Compressor start needs C. Wire for an AC.
AC, plate 12–16 A4 sq mmC204 sq mm carries 24 A in a pipe, so 20 A fits. Above 16 A, send us the plate.
Water pumpown lineby plateC16 / C20Same plate rule as the AC: up to 12 A on 2.5 sq mm with C16, 12–16 A on 4 sq mm with C20. Wire for a pump.
Main4 or 6 sq mmDP 20 / 25Double pole, sized to the sanctioned load and the main wire. Below.
RCCBafter the main30 mA DPAmps equal to or above the main. Below.
Why this chart says 16 A where others say 20 AMany charts online put 20 A on 2.5 sq mm. V-Guard, whose wire we sell, rates Classo+ 2.5 sq mm at 18 A inside a wall pipe and 22 A only when clipped on the surface. House wiring here runs in pipes in the wall, so we use 18 A and put 16 A on it. Finolex prints the same 18 A for its 2.5 sq mm. The safer number wins.
The MCB must sit inside the wire
Wire current limit against MCB rating Bars show the current each wire carries inside a pipe: 1 sq mm 11 A, 1.5 sq mm 13 A, 2.5 sq mm 18 A, 4 sq mm 24 A, 6 sq mm 31 A. The right MCB sits inside each bar: 6 A, 10 A, 16 A, 20 A and 25 A. The common wrong choices sit outside it: 16 A on 1 and 1.5 sq mm, 20 A on 2.5, 25 A on 4 and 32 A on 6. carries in a pipe right MCB ✗ too big 1 sq mm1.5 sq mm2.5 sq mm4 sq mm6 sq mm 11 A13 A18 A24 A31 A 610162025 ✗16✗16✗20✗25✗32 0 A102030
Two wires in a pipe. 1 to 4 sq mm: V-Guard Classo+ product page. 6 sq mm: Finolex FR wire sheet (31 A in a pipe, 37 A clipped); Finolex prints the same figures as V-Guard for the smaller sizes. 1 sq mm can also take B10 (inside 11 A); B6 leaves more room.
The letter on the MCB

B or C: the amps stay the same, only the start changes

A B16 and a C16 both carry 16 A all day. The letter sets how big a sudden surge the MCB lets pass before it snaps off. V-Guard's Elegna sheet gives the bands.

BLights, fans, plain sockets

Trips at once at 3 to 5 times its rating. Quicker on a short in a thin light wire, and nothing on these circuits starts with a big surge.

CAnything with a motor

Waits until 5 to 10 times its rating. AC compressor, fridge, pump, mixer and washing machine pull a burst as they start; a B-curve reads it as a fault and drops.

16 AGeyser and heater

A heating element has no start surge, so B or C both work. The piece for a geyser is 16 A double-pole, as CPWD's wiring specification recommends for water heaters, and it takes two ways on the board.

D-curve is for heavy factory motors, not houses. If a correct C-curve still trips as a motor starts, the motor is the problem, not the MCB: MCB tripping again and again. The full B vs C story: B curve vs C curve MCB.

The main switch

The main: double pole, sized to your sanctioned load and your main wire

Circuit MCBs are single pole (SP): they cut the phase. The geyser's is double pole, like the main. The main is double pole (DP): it cuts phase and neutral together, so the house is fully dead when you switch it off. More in SP vs DP MCB.

1. Find your amps

Your sanctioned load is on the NBPDCL bill, in kW. Multiply by 1,000 and divide by 230.

5 kW × 1,000 ÷ 230 = 21.7 A. The main must be at least this.

2. Check the main wire

The main can't be bigger than the wire from the meter carries in its pipe: 4 sq mm 24 A, 6 sq mm 31 A.

21.7 A needs a DP 25 A, and DP 25 A needs 6 sq mm.
Sanctioned loadMain MCBMain wire
up to 4.6 kWup to 20 ADP 20 A4 sq mm at least; 6 sq mm if you will add an AC later
4.6 to 5.75 kW20 to 25 ADP 25 A6 sq mm
above 5.75 kWover 25 Asend us the loadNeeds a heavier main or a three-phase connection

"My MCBs add up to 100 A. Is a 25 A main too small?"

No. That is normal. A board might hold B10 + B10 + C16 + 16 A DP + C16 + C20 + C16 = 104 A of MCBs, but they never all run full at once: the lights don't draw 10 A, the geyser runs twenty minutes. The main is sized to what the house really draws together, which is what the sanctioned load is meant to cover.

  • If the main trips on hot evenings with two ACs, the geyser and the pump together, the house has outgrown its load. Apply to NBPDCL for more kW and size the main and its wire again. Meter and sanctioned load.
  • Never fit a bigger main on the same wire to stop it tripping. The main wire is the hardest wire in the house to change later.
  • V-Guard makes the Elegna in double pole as well as single pole (its spec sheet). The DP main is ordered for you.
RCCB

The RCCB protects people. The MCB never will.

An MCB only feels big currents: an overload or a short. A leak through someone's hand is far too small for it to notice. An RCCB compares what goes out on the phase with what comes back on the neutral, and switches off when the difference is 30 mA.

Which one

  • 30 mA, double pole for a house. V-Guard's Invidia range also comes in 100 and 300 mA; those are for fire protection on big installations, not for people.
  • Amps equal to or above the main: DP 20 or 25 A main → 25 A RCCB. It has no overload protection of its own; the main does that job.
  • V-Guard makes it in 16, 20, 25, 32, 40 and 63 A. Ordered for you.

Where and how

  • Right after the main DP, before the circuit MCBs.
  • It needs the neutrals kept apart: every circuit's neutral must come back through it. A neutral borrowed from another circuit makes it trip for no reason.
  • It trips on a leak; the house earthing is what gives the leak a safe path. Earthing basics.
  • Press the T button once a month (usual practice; follow the leaflet in the box). It should drop at once.
Old house with leaky wiring? One 30 mA RCCB on everything can trip often. V-Guard's sheet says it may trip from half its rating, 15 mA. Then split it: one RCCB for bathrooms, kitchen and outside points. MCB vs RCCB.
What the RCCB watches
How an RCCB detects leakage The phase carries 10 amps out to a geyser and the neutral brings 9.97 amps back. The missing 30 milliamps leaks through the geyser body to earth or through a person. The RCCB sees the difference and trips. RCCB out − back out 10.000 A back 9.970 A Geyser worn element 30 mA leaks to earth, or through a hand difference 30 mA → OFF
The ring inside the RCCB feels the difference between the two wires. An MCB on the same line sees only 10 A, well under its rating, and stays on. Ratings: V-Guard Invidia RCCB sheet.
Board layout

How the circuits are split on the board

The order on the rail is the order in the drawing at the top: main, RCCB, then one SP MCB per circuit (a DP for the geyser). How you split the circuits matters more than the order.

One heavy load, one MCB

  • Each AC, each geyser and the pump gets its own line from the board, with its own MCB. Never off a room's light or socket circuit.
  • The kitchen gets its own C16.
  • A tripped AC then darkens nothing else, and the electrician can find a fault in minutes.

Split by floor

  • Lights and fans: one B10 per floor. 6 A sockets: one B10 per floor. 16 A sockets: one C16 per floor.
  • A floor with many rooms can take two light circuits; the wire still decides the MCB.
  • Building up later? Leave the first floor's ways empty on the board now.

Inverter side and mains side

  • With an inverter, the circuits it runs (lights, fans, a few 6 A sockets) are fed from its output. Keep AC, geyser and pump on the mains side only.
  • Plan this before wiring, so those circuits come back to the board separately. Inverter wiring points.

Ways in the DB box

  • Count one way for every SP MCB and two for each geyser's DP, then add two spare.
  • The main DP and the RCCB need space for two modules each, on top of that.
  • Mount it dry, near the meter, at hand height. The full guide: distribution board for a house.
The builder below counts the ways for your house.
What goes wrong

Six board mistakes we see, and what they cost

Most of these work for months. They show up on the first night of real load, or the day someone gets a shock.

C20 2.5 sq mm · carries 18 A

20 A MCB on 2.5 sq mm

You see: nothing, until the insulation cooks

Between 18 and 20 A the wire runs hot in the wall and nothing trips. Use 16 A on 2.5, or run 4 sq mm for 20 A.

B16 1.5 sq mm · carries 13 A

16 A on the light circuit

You see: a heater plugged into a light point and no trip

1.5 sq mm carries 13 A in a pipe. Its MCB is B10. A 16 A there protects nothing.

C32 lights, fansACgeyser, sockets

One big MCB for a whole floor

You see: the floor goes dark when the AC starts

A big MCB to stop that tripping leaves every thin wire on it unprotected. Split the circuits: one MCB per heavy load.

B16 M start surge

B-curve on the pump or AC

You see: the MCB drops every time the motor starts

Same amps, letter C. Don't go up in amps to stop it.

LN ! still live

MCB in the neutral wire

You see: a shock from a fitting that was "switched off"

An SP MCB must sit in the phase (red). If it is in the neutral, the light goes off but the wire stays live.

RCCB T RCCB 16 Abehind a25 A main

RCCB smaller than the main, or never tested

You see: a burnt RCCB, or one that doesn't trip

The RCCB must be rated at or above the main. Press T once a month; if it doesn't drop, replace it.

Build your board

Your MCB list and DB size

Tell us what the house has. You get every MCB with its letter and wire, the main, the RCCB and the number of ways for the DB box. Read your AC and pump plates for their amps.

16 A socket lines: usually one per floor (washing machine, iron, heater). Lights, fans and 6 A sockets are added automatically, one circuit each per floor. Over 16 A on any plate: send it to us first.

Your board

DB box—
Send this board to Sashikesh

Rules: wire limits from V-Guard Classo+ (Finolex for 6 sq mm), MCB curves from the Elegna sheet, RCCB ratings from V-Guard's Invidia sheet. Prices Ask rate each, filled in from today's rate. Wire metres for the whole house: wiring calculator.

On our shelf for this job

MCBs, RCCB and the wire behind them

Anything not on the shelf, we order for you; ask on WhatsApp for the time it takes. Every piece comes on a GST bill with the box QR you can check on V-Guard's site (asli ya nakli MCB). Today's prices: electrical rates.

Questions people ask us

Short answers

Which MCB for a 1.5 ton AC? (1.5 ton AC ke liye kitne ampere ka MCB)

Go by the current on the AC's name plate. Up to 12 A, which is most 1 and 1.5 ton splits: 2.5 sq mm wire and a 16 A C-curve MCB. From 12 to 16 A: 4 sq mm wire and a 20 A C-curve MCB. Above 16 A, send us the plate. Every AC gets its own MCB. Details: wire for an AC.

Which MCB for a geyser?

A 2 kW geyser draws about 9 A and a 3 kW one about 13 A, so both go on 2.5 sq mm wire with a 16 A double-pole MCB, B or C curve; CPWD's wiring specification (Part I, 2013, cl. 3.14) recommends double-pole protection for water heaters, and a DP takes two ways on the board. Not 20 A: 2.5 sq mm in a wall pipe carries 18 A (V-Guard Classo+).

16 A or 20 A MCB on 2.5 sq mm wire?

16 A. V-Guard rates Classo+ 2.5 sq mm at 18 A inside a pipe, so a 20 A MCB would let the wire run hot without tripping. A 20 A MCB goes only on 4 sq mm, which carries 24 A in a pipe.

Which MCB for lights and fans?

A 10 A B-curve MCB on 1.5 sq mm wire, or a 6 A B-curve on 1 sq mm. Never 16 A on 1.5 sq mm, which carries only 13 A in a pipe.

What size main MCB for a house?

A double-pole (DP) MCB. It must be at least your sanctioned load in amps (kW × 1,000 ÷ 230) and no bigger than the main wire carries: up to DP 20 A on 4 sq mm, up to DP 25 A on 6 sq mm in a pipe. Above about 5.75 kW, send us the load: it needs a heavier main or a three-phase connection.

Does a house need an RCCB as well as MCBs?

Yes. Regulation 44 of the Central Electricity Authority (Measures relating to Safety and Electric Supply) Regulations, 2023 requires a residual current device of not more than 30 mA in a domestic installation. An MCB protects the wire from overload and short circuit; it does not feel a small leak through a person. A 30 mA double-pole RCCB, fitted after the main, switches off when current leaks to earth. Its rating should be equal to or above the main MCB.

B curve or C curve for home?

B for lights, fans and plain sockets. C for anything with a motor or compressor: AC, fridge, kitchen, washing machine and water pump. The curve never changes the amps; those come from the wire.

How many MCBs for a 2 BHK on one floor?

Usually: B10 lights and fans, B10 6 A sockets, C16 16 A sockets, C16 kitchen, 16 A double-pole geyser, C16 for each AC, C16 for the pump: about 6 SP MCBs and one DP for the geyser, plus the DP main and an RCCB. Put your own house into the builder above.

My MCB keeps tripping. Can I put a bigger one?

No. A bigger MCB stops the tripping by letting the wire overheat. Find the cause: MCB tripping again and again.

Sashikesh Kumar
Diploma in Electrical, Tashya Ventures

Looks after wires, switchgear, inverters and pumps at our Reva Road store, Muzaffarpur. The MCB, RCCB and wire figures on this page were checked against V-Guard's own sheets on 13 Nov 2026. Where a rule could go two ways, the page gives the safer one.

Where the numbers come from

  1. V-Guard, Classo+ house wire product page: two wires, current in conduit / clipped: 1 sq mm 11 / 12 A, 1.5 sq mm 13 / 16 A, 2.5 sq mm 18 / 22 A, 4 sq mm 24 / 29 A.
  2. V-Guard, Elegna MCB technical specification: SP, DP, SPN, TP, FP, TPN; 6, 10, 16, 20, 25, 32, 40 and 63 A; B type 3–5 In, C type 5–10 In; 10 kA, IS/IEC 60898-1. Warranty: Elegna product page.
  3. V-Guard, Invidia RCCB specification: type AC, 2 and 4 pole, 16 to 63 A, 30, 100 and 300 mA, non-operating current 0.5 I∆n.
  4. Finolex, FR PVC wire data sheet: 6 sq mm, 31 A in conduit, 37 A clipped (two wires, single phase); smaller sizes match V-Guard's figures.
  5. Earth wire the same size as the phase wire: standard wiring practice, IS 732.

Send us your circuit list

Or a photo of your board. Sashikesh will send back the MCBs, the main and the RCCB, with today's price, on WhatsApp.