2.5 sq mm wire in Muzaffarpur: 16 A sockets, kitchen, geyser and small AC, 18 A in a pipe, 90 m coil

The short answer

2.5 sq mm is the wire for sockets and heavier points. V-Guard Classo+ 2.5 sq mm carries 18 A in a wall pipe (22 A clipped in open air), so it takes a 16 A MCB, never 20 A. Use it for 16 A sockets, the kitchen, the geyser (16 A double-pole MCB) and a 1 ton or 1.5 ton split AC whose name plate says up to 12 A (16 A C-curve MCB). Over 12 A, take 4 sq mm.

18 A
in a wall pipe22 A clipped in the open (V-Guard).
16 A
MCB in frontPlan up to 3,680 W on the circuit.
90 m
one coilBlack on the shelf; other colours we order.
Ask rateClasso+ 2.5 sq mm, 90 m coil, with GST. Per metre: coil price ÷ 90.
Today's price on the wire price list
One ruler: where 2.5 sq mm stops
Wire amps and MCB on one rulerA ruler from 0 to 26 amps. The MCB trips at 16 A, the wire carries 18 A in a wall pipe and 22 A clipped in the open.02468101214161820222426Asafe load16 A MCBtrips here18 Awire limit in a wall pipe22 Aclipped, open air20 A never
A 16 A MCB trips before the wire reaches 18 A. A 20 A MCB sits above the wire's pipe limit, so the wire cooks inside the wall and the MCB never trips.
What it feeds

Put it on these, move size for those

Put 2.5 sq mm on

Power circuits

  • 16 A sockets: mixer, iron, cooler, washing machine (thick-pin plug).
  • The kitchen line, on its own 16 A MCB.
  • The geyser: its own line, 16 A double-pole MCB.
  • A 1 ton or 1.5 ton split AC with name plate up to 12 A.
  • A small water pump, sized from its name plate.
Earth wire for these circuits is also 2.5 sq mm, in green: the same size as the phase (IS 732).
Change the size

When 2.5 is wrong

  • AC with name plate 12 to 16 A, or a long pump run: 4 sq mm, 20 A MCB.
  • Lights, fans and 6 A sockets only: save the money, use 1.5 sq mm.
  • Two heavy loads on one 2.5 line (geyser plus a socket line): split into two lines.
  • MCB keeps tripping: find the load, never fit a bigger MCB: MCB tripping again and again.
The wire stays 2.5 sq mm. The MCB stays 16 A.

Which size for every point in a house, side by side: 1.5 vs 2.5 sq mm wire.

Amps and MCB

The numbers for 2.5 sq mm Classo+

V-Guard prints a current figure for Classo+; most wire makers' pages print none. The full chart for every size is the wire amps chart.

WhatFigureWhat it means
In a wall pipe18 AThe figure to use in a house; about 4,140 W at 230 V.
Clipped, open air22 ANot for a house: even the bit near the board counts as in-pipe.
MCB in front16 APlan the load up to 3,680 W, about 3,600 W in practice. Never 20 A.
Strands × mm, overall width48 × 0.25 · 3.4 mmSoft multi-strand; insulation 0.7 mm.
Max resistance7.98 Ω/kmThe number to hold the wire to.
Copper in a 90 m coil~2.0 kgOur own sum from the size, so the price follows copper.
Why not 20 AThe MCB protects the wire, so it is chosen from the wire's in-pipe amps (18 A) and set one standard step below (16 A). The geyser or AC only has to fit under it. Some sites pair 2.5 sq mm with a 20 A breaker; that is above V-Guard's figure for a wire in a pipe, and a Bihar wall in May is already hot. Rule: wire amps chart; room by room: which MCB for which load.
AC and geyser

A 1 ton or 1.5 ton AC: read the plate, then pick

Most split ACs here are 1 ton or 1.5 ton. Read the amps on the name plate, then find the box below.

AC name-plate amps → wire → MCB
AC name-plate amps decide the wireUp to 12 amps on the name plate: 2.5 sq mm and a 16 A C-curve MCB. 12 to 16 amps: 4 sq mm and a 20 A C-curve MCB. Above 16 amps: send us the plate.Read the amps on the AC name plate≤ 12 A2.5 sq mm16 A C-curve MCBThis page12 – 16 A4 sq mm20 A C-curve MCBNext size up> 16 Asend us the platewe size it with youUse the name-plate amps, not the watts: watts ÷ 230 understates what an AC really draws.
An AC has a motor, so it takes a C-curve MCB: the start surge does not trip it. Lights, sockets and geysers take B-curve.
The geyser has its own lineA geyser runs for long stretches at full load, so it gets 2.5 sq mm straight from the board and a 16 A double-pole MCB, which cuts both phase and neutral. Keep it off the socket circuit. Wire for a geyser · wire for an AC.
How many coils

2.5 sq mm coils for your house

Like every size, 2.5 sq mm is bought as red, black and green: one coil of each is the smallest order. That is why a one-room house and a three-room house both come to three coils.

House (single floor unless stated)2.5 sq mm coilsWire used
1 room, kitchen, bath3~83 m
2 rooms, kitchen, bath, AC, geyser, pump3~218 m
3 rooms, kitchen, 2 baths, AC, geyser, pump3~238 m
Two floors, 2 rooms each6~375 m
Three floors, 2 rooms each9~693 m

Usual practice with 10% spare, from our coil guide; your electrician's point list decides the final count. Counter: wiring calculator. Pipe for 2.5 sq mm runs is 25 mm: conduit pipes.

Our shelf

2.5 sq mm at our store, with today's price

Every coil goes out on a GST bill. Other colours, other makes and any MCB rating we can order for you; ask on WhatsApp for the time it takes. All sizes in one place: wire price list. Delivery is charged separately; ask for the amount for your site (delivery).

Why sites differ

Online, the amps for 2.5 sq mm run from 10 A to 25 A

We read what sites say about 2.5 sq mm on 18 Nov 2026. Here is the spread, and the figure we stand by.

SourceAmpsMCBGap
NoBroker forum10 AnoneLower than V-Guard's figure for 1.5 sq mm; no MCB.
Joca Cable blog20–25 A20 AForeign standards (IEC, NEC, BS); 20 A is above V-Guard's 18 A pipe figure.
Polycab product pagenonenoneMRP only, no amps and no circuit advice.
Tashya (V-Guard Classo+)18 A pipe · 22 A clip16 APipe figure, MCB, AC, geyser, coils and colours on one page.
When makers disagree, take the lower numberA wire run a little under its limit lasts; one run at the top of a table measured in cool open air does not. We take V-Guard's pipe figure, because our wires go in pipes in hot walls. Polycab's page shows an MRP of ₹11,200 for a 90 m coil of one premium range; compare prices only within one make and range.
Questions people ask us

Short answers

What is the 2.5 sq mm wire price in Muzaffarpur?

Today's price for a 90 m coil of Classo+ 2.5 sq mm, with GST, is on the wire price list, updated each morning. Divide by 90 for the price per metre. The black coil is on the shelf; other colours we order.

How many amps does 2.5 sq mm wire carry, and which MCB?

V-Guard's Classo+ table: 18 A in a wall pipe, 22 A clipped in the open. Use 18 A, with a 16 A MCB. Never 20 A: between 18 and 20 A the wire heats inside the wall and a 20 A MCB does not trip.

Can a geyser run on 2.5 sq mm?

Yes: its own 2.5 sq mm line from the board, with a 16 A double-pole MCB, as CPWD's wiring specification recommends for water heaters. Do not share it with a socket line. Geyser wire in detail.

Is 2.5 sq mm enough for a 1.5 ton AC?

Go by the name plate. Up to 12 A: 2.5 sq mm and a 16 A C-curve MCB. 12 to 16 A: 4 sq mm and 20 A. Above 16 A, send us the plate. The arithmetic: wire size for an AC.

Can I put a 20 A MCB on 2.5 sq mm?

No. 20 A goes only on 4 sq mm. Some websites suggest 20 A for 2.5 sq mm; that is above V-Guard's 18 A pipe figure.

How much can one 2.5 sq mm kitchen line carry?

With a 16 A MCB, plan up to 3,680 W in all on that line. A geyser or oven on the same wall should get its own line.

Sashikesh Kumar
Diploma in Electrical, Tashya Ventures

Looks after wires, switchgear, inverters and pumps at our Rewa Road store, Muzaffarpur. The amp figures are V-Guard's own, checked on 18 Nov 2026. Where makers disagree, this page says so and takes the safer figure.

Where the numbers come from

  1. V-Guard, Classo+ triple layer insulation wire: 18 A in a wall pipe and 22 A clipped for 2.5 sq mm, 48 × 0.25 mm strands, 3.4 mm overall, 0.7 mm insulation, 7.98 Ω/km, 70 °C, 1100 V.
  2. MCB at or below the in-pipe figure, earth the same size as phase (IS 732), coil counts and pipe lengths: our own wire amps chart and coil guide, linked above.
  3. Geyser on a 16 A double-pole MCB: CPWD's wiring specification, as cited in our coil guide.
  4. Other sites read on 18 Nov 2026: NoBroker, Joca Cable, Polycab.
  5. Store facts: our own shelf at Rewa Road; colours as on our last supplier bill.

Tell us your points, we'll tell you the coils

Send the number of sockets, ACs and geysers, with the AC name-plate amps. We reply with the coils by size and colour, and one price for the lot.

TASHYABUILDING SOLUTIONS · MUZAFFARPUR
WhatsApp 90310 74624tashyaventures.com