Home›Guides›Plumbing›Geyser line
Plumbing guide · bathroom

Geyser line: which pipe, the safety valve, the wire and MCB, and how to run it in the wall

The short answer
  • CPVC on the hot sideFrom the geyser outlet to the shower mixer, the basin and every hot tap. Also the last stretch of cold pipe into the geyser.
  • UPVC on the cold sideTank to bathroom, tank to every cold tap. It stops at 60 °C, so never after the geyser.
  • Safety valve on the cold inletScrewed straight onto the geyser. It drips; that is normal. Never plug it.
  • Its own electric line2.5 sq mm wire, 16 A double-pole MCB, a proper earth, and the house's 30 mA RCCB.

Most geyser trouble starts in the wall, not in the geyser: the wrong pipe on the hot side, glue where a thread should be, or a dripping valve somebody plugged. Lay the lines right before the tiles go on, because after that every fix means breaking tiles.

82 °C
CPVC's limitPrince SmartFit Plus. A geyser thermostat goes up to 75 °C.
8 bar
Safety valveOpens before the tank's rated pressure is passed (A. O. Smith, Havells).
16 A
Double-pole MCB on 2.5 sq mmFits a 2 kW (8.7 A) or 3 kW (13 A) geyser. Never 20 A.
One bathroom wall, done right
Geyser connections on a bathroom wall A geyser hangs high on the wall. UPVC cold pipe comes down from the roof tank on the right, feeds the cold side of the shower mixer, and turns into CPVC for the last stretch to the geyser's cold inlet, where a brass safety valve is fitted. Its drain tube runs down to the floor trap. Red CPVC leaves the geyser's hot outlet and runs straight down the wall to the hot side of the mixer, on the left. A 16 A double-pole switch sits high on the wall, above 2 m, fed by its own wire from the board; there is no socket in the bathroom. GEYSER CPVC MIXER hot left cold right from roof tank floor trap 1 2 3 4 5 6
  1. 1CPVC hot line from the geyser outlet straight down to the mixer's left side.
  2. 2UPVC cold line from the tank, to the mixer's right side and towards the geyser.
  3. 3Safety valve on the geyser's cold inlet; its drain tube goes to the floor trap.
  4. 4Braided hoses from geyser to wall points with brass threads.
  5. 5Thread joint where UPVC becomes CPVC for the last stretch into the geyser.
  6. 616 A double-pole switch outside the bathroom door, or inside above 2 m, on its own line. No socket in the bathroom.
Not to scale. Hoses: A. O. Smith asks for nylon or steel-braided hoses rated at least 8 bar and fit for hot water. Hot on the left, cold on the right is the usual layout of Indian mixers; check yours.
The hot side

Why the line after the geyser has to be CPVC

A geyser's thermostat can be turned up to 75 °C on the A. O. Smith model we checked. UPVC is rated only to 60 °C. CPVC is rated to 82 °C by Prince. Only CPVC covers the whole range the geyser can send.

  • UPVC after a geyser softens when hot water runs, sags between its clamps and loosens at the joints. The leak usually starts behind the tiles, months later.
  • Prince says 82 °C, Ashirvad says 93 °C. We go by the lower figure, from Prince's product page. In practice, keep the geyser thermostat well below 82 °C.
  • Hot water also burns. A. O. Smith warns that water above 52 °C can scald at once. A setting around the middle of the dial is plenty for a bath; it also saves power.
  • CPVC only where it is hot. CPVC costs more, so the cold supply stays UPVC. Most houses use both pipes; the full comparison is on CPVC vs UPVC vs PVC vs GI.

Usual practice: the last metre or so of the cold pipe into the geyser is also CPVC, because the heat creeps back up the inlet when the geyser runs and no tap is open.

Temperature ratings against what a geyser sends A scale from 0 to 100 °C. UPVC is rated from 5 to 60 °C. A geyser thermostat can be set from 25 to 75 °C. CPVC is rated to 82 °C by Prince and 93 °C by Ashirvad. Water above 52 °C can scald. UPVC Geyser CPVC 5–60 °C · Prince Easyfit thermostat 25–75 °C · A. O. Smith 82 °C Prince · 93 °C Ashirvad ONLY CPVC scalds above 52 °C 020406080100 °C
Makers' figures: Prince SmartFit Plus and Easyfit pages, Ashirvad FlowGuard Plus page, A. O. Smith Elegance Slim Neo manual (25–75 °C setting, scald warning above 52 °C).
Connecting the geyser

The geyser corner, part by part

The geyser hangs on the wall; the pipes are inside it. Between them sit three short parts, and each one has a right way.

Cold side, from the wall to the geyser
Close-up of the geyser's cold connection Inside the wall, a CPVC pipe ends in a brass-threaded CPVC elbow flush with the tile. A braided hose screws onto it with Teflon tape on the threads, rises to the multi-function safety valve, and the valve screws into the geyser's cold inlet, marked with a blue sticker. The valve has a lever and a drain outlet with a tube going down. WALL GEYSER (bottom) cold inlet · blue sticker lever: lift now and then drain tube to floor trap, never plugged braided hose 8 bar, hot-water rated brass-threaded CPVC elbow at tile face Teflon onthreads valve
The hot side is the same without the valve: hot outlet (red sticker) → braided hose → brass-threaded CPVC elbow → CPVC in the wall. Valve, sticker colours, hose rating: A. O. Smith manual.
  1. The wall point: brass threads, glued onto CPVCThe CPVC line ends at the tile face in a female-threaded elbow or adaptor with a brass insert. Prince lists these heavy brass-insert MTA and FTA fittings in its SmartFit Plus range. A plastic thread on the hot side is the one that cracks first. More on these parts: MTA and FTA adaptors.
  2. The hose: braided, 8 bar, hot-water ratedA. O. Smith asks for nylon or stainless-steel braided hoses rated at least 8 bar and suitable for hot water. Plain plastic tube from the market is not that. Keep the hose short and without kinks.
  3. The threads: Teflon tape, never solventWrap the male thread clockwise, a few turns, as the A. O. Smith manual says. Tape goes on threads only. Solvent goes on CPVC sockets only.
  4. The geyser's own threadsThe model we checked has ½″ BSP inlet and outlet. Blue sticker is cold in, red sticker is hot out. Swap them and the geyser sends cold water to the shower first.
  5. Where UPVC meets CPVCA ½″ CPVC pipe is 15.9 mm across; a ½″ Easyfit UPVC pipe is 21.3 mm. They don't fit each other. Join them through threads: UPVC male adaptor on one side, brass-threaded CPVC adaptor on the other, each glued with its own solvent. Details on the pipe comparison.
  6. Every CPVC joint: CPVC solvent, 24 hours, then testCut square, chamfer, deburr, brush the yellow CPVC cement on, push home, hold 1–2 minutes. Prince says wait 24 hours before a pressure test. Step by step: how to join CPVC pipe.
The part people plug

The safety valve: what it does, and why it drips

Every storage geyser comes with a brass valve for its cold inlet. Havells and A. O. Smith call it a multi-function valve: it lets out pressure, stops hot water from flowing back up the cold pipe, and lets air in when the tank is drained.

Why it drips

Water grows a little as it heats. The non-return part stops it going back up the cold pipe, so the extra comes out of the valve's drain, a few drops at a time. A. O. Smith says this dripping is normal.

Drips while heating: normal. A steady stream: call the geyser's service centre.

Never plug it

  • Not with a cap, not with a stick, not by taking the valve off. A. O. Smith says it must never be removed or blocked, and doing so voids the warranty.
  • A plugged valve leaves the thermostat as the only thing between the tank and its rated pressure.
  • Lead the drain with a thin tube to the floor trap, so the drip doesn't run down the tiles.

Fitting and care

  • It screws straight onto the geyser's cold inlet, with nothing in between. Don't strain it while tightening.
  • Lift the lever now and then to clear scale; A. O. Smith asks for this regularly. Hard water from a boring scales it faster.
  • A separate non-return valve on the cold line, if any, goes well back from the geyser: A. O. Smith says at least 40 ft away.
Roof tank or pressure pump? A house fed from a roof tank has low pressure at the geyser, so the valve rarely opens for pressure. With a pressure pump, the valve matters more: the geysers we checked are rated 8 bar (0.8 MPa), and A. O. Smith gives 0.8 MPa as the highest inlet pressure. Keep the pump's cut-off well below that. See pressure pump for home.
The electric side

Wire and MCB: a geyser gets its own line

A geyser draws a steady current for an hour at a stretch in winter. That is what heats a thin wire or a loose socket. Give it its own circuit from the board.

GeyserDrawsWireMCB
2 kWe.g. A. O. Smith 15 L storage8.7 A2.5 sq mm × 316 A DP
3 kWe.g. Havells 6 L Instanio Prime13 A2.5 sq mm × 316 A DP
Above 3.5 kWread the name plate15 A +Send us the plate on WhatsApp

Amps = watts ÷ 230. Havells prints 13.04 A for its 3 kW Instanio Prime, which matches. V-Guard Classo+ 2.5 sq mm carries 18 A in a wall pipe, so the MCB is 16 A double-pole, never 20 A: between 18 and 20 A the wire overheats and a 20 A MCB never trips. B-curve is fine for a heater. Double-pole is what CPWD's wiring specification (Part I, 2013, cl. 3.14) recommends for water heaters: it cuts phase and neutral together. Earth wire the same size as phase and neutral.

The switch for the geyser

  • No socket in the bathroom. CPWD's specification allows none for portable appliances there, only a switch for a fixed appliance such as a geyser.
  • A 16 A double-pole switch on its own line: outside the bathroom door, or inside the bathroom only above 2 m and at least 1 m from the shower. The geyser is wired through it directly.
  • A. O. Smith: its own separate supply, no adaptor or extension board, and reliable earthing.
  • Switch on only after the geyser is full of water; the manual says so too.
  • At the board: a 30 mA RCCB, which the CEA safety regulations of 2023 require in every home. More on which MCB for which load.

Amps for every wire size: wire amps chart.

From the board to the geyser
Geyser circuit From the distribution board: the 30 mA RCCB, then a 16 A double-pole MCB for the geyser alone, then three 2.5 sq mm wires, phase, neutral and earth, through a pipe in the wall to a 16 A double-pole switch for the geyser, outside the bathroom door or above 2 m. The earth wire runs to the earth bar and the earth pit. BOARD RCCB 30 mA DP MCB 16 A earth bar → earth pit 2.5 sq mm × 3 phase · neutral · earthin a wall pipe 16 A DP switch GEYSER 2 kW · 8.7 A phase neutral earth 16 A trips before 18 A, the wire's limit.
Wire limit: V-Guard Classo+ table (2.5 sq mm, 18 A in conduit). RCCB: CEA (Measures relating to Safety and Electric Supply) Regulations 2023, reg. 44. Wire colours as usual practice; check yours.
Before plaster and tiles

Running hot and cold lines side by side in the wall

Once the wall is tiled, nobody can see the pipes again. These rules are what keep a drill bit, a nail or a leak out of them.

Right and wrong chase cutting
Pipe routes in a bathroom wall Left panel, right way: hot CPVC and cold UPVC run only straight up, down and across, side by side with a gap, hot on the left, to the mixer and the basin. Right panel, wrong way: a pipe runs diagonally across the wall where a drill for a towel rail later hits it. shower mixer basin gap drill for towel rail hits the hot line STRAIGHT LINES DIAGONAL
Red: CPVC hot. Blue: UPVC cold. Straight runs and a gap between hot and cold are usual practice, so anyone can guess where a pipe is from the tap above it.
  1. Geyser close to the showerEvery metre of hot pipe holds cold water you run off before the hot arrives, every time. A ½″ CPVC pipe holds about 0.13 litre per metre (worked out from Prince's SDR 11 size). Put the geyser on the shower wall, not across the room.
  2. Straight up, down and acrossNo diagonal runs. A pipe that goes straight up from a tap can be found later; a diagonal one gets drilled into for a towel rail or a mirror.
  3. Hot left, cold right, with a gapMatches the mixer. A finger's gap or more between the two lines, so the cold doesn't pick up heat and the hot doesn't lose it (usual practice).
  4. Away from the wiringKeep the hot line out of the electrical pipe's chase. Water and wire never share a groove.
  5. Test before you plasterFill the lines and leave them under pressure, after the 24 hours Prince asks for after the last CPVC joint. Look at every joint. Only then plaster and tile.
  6. Photograph the open wallTake photos with a tape measure in them before plaster. They show where the pipes are for the next twenty years. Send them to us on WhatsApp and we will look at them with you.
Water wasted before the hot arrives, with ½″ CPVC 3 m of pipe: about 0.4 L · 6 m: about 0.8 L · 10 m: about 1.3 L, each time a tap is opened. Four baths a day on a 10 m run is over 150 litres a month that the pump lifted for nothing. Waterproofing the floor and wall before tiling: bathroom waterproofing.
What goes wrong

Six geyser-line mistakes we see in Muzaffarpur

UPVC after the geyser

Later: a weeping joint inside the tiles

Easyfit is rated to 60 °C. Cheaper on the day, costly when the tiles come off. The hot side is CPVC.

One solvent tin for both pipes

Later: hot joints that let go

CPVC needs CPVC cement; UPVC its own. Keep two tins on site, labelled. See solvents and tapes.

Safety valve plugged

Later: a tank with no pressure relief

The drip annoys someone, so the drain gets capped. Lead it to the floor trap instead. A. O. Smith says blocking it voids the warranty.

Geyser on a board or a 6 A socket

Later: a burnt plug and socket

A 2 kW geyser draws 8.7 A for an hour at a time. It needs its own 16 A double-pole point on 2.5 sq mm wire. MCB tripping?

No earth at the geyser point

Later: a shock from the tap

The earth wire must reach the geyser point, and the RCCB must trip when its test button is pressed. Check both before the geyser goes on.

Plastic threads on the hot side

Later: a cracked adaptor at the wall

Use brass-insert threaded CPVC fittings at the geyser and mixer points, and Teflon on the threads, not solvent. Leaking joint?

Questions people ask us

Short answers

Which pipe for the geyser line? (geyser ki line mein kaun sa pipe)

CPVC, from the geyser outlet to every hot tap and the shower mixer. Prince rates its SmartFit Plus CPVC up to 82 °C. UPVC such as Prince Easyfit is rated only from 5 to 60 °C, and a geyser thermostat can be set as high as 75 °C (A. O. Smith manual).

Can UPVC be used for the geyser line?

No. Prince rates Easyfit UPVC for 5 to 60 °C. Geyser water can be hotter, and the pipe softens and the joints start to weep, usually inside the tiled wall. The cold supply to the bathroom stays UPVC.

Why does the geyser valve drip?

Water expands as it heats. The valve's non-return part stops it going back up the cold pipe, so a little escapes from the valve's drain. A. O. Smith says this dripping is normal. Never plug or remove the valve; lead its drain to the floor trap instead. A steady stream, not drops, is a fault: call the geyser's service centre.

Which wire and MCB for a geyser?

Its own line of 2.5 sq mm wire (phase, neutral and earth) on a 16 A double-pole MCB. A 2 kW geyser draws about 8.7 A and a 3 kW geyser about 13 A, both inside 16 A. V-Guard Classo+ 2.5 sq mm carries 18 A in a wall pipe, so never put a 20 A MCB on it. Full table: wire amps chart.

What size is the geyser pipe?

Half inch for the geyser connection and for each tap; the geyser's inlet and outlet are ½″ BSP threads on the A. O. Smith model we checked. A half-inch CPVC pipe is 15.9 mm outside and a half-inch Easyfit UPVC pipe is 21.3 mm, so they join through threaded adaptors, not glue.

Is the cold pipe into the geyser also CPVC?

Usual practice is to make the last stretch of the cold pipe into the geyser CPVC too, because heat creeps back up the inlet. The rest of the cold supply stays UPVC.

Can the geyser be connected straight to the CPVC pipe, without a hose?

The manual we checked asks for braided flexible hoses rated at least 8 bar. A hose also lets the geyser come off the wall for service without cutting any pipe. So: CPVC in the wall, brass-threaded point at the tile, braided hose to the geyser.

Arun Tiwari
Thekedar · site work, costs and plumbing, Tashya Ventures

Twenty years on sites around Muzaffarpur, including more re-tiled bathrooms than he would like, most of them for a UPVC pipe behind a geyser. Every figure on this page was checked against the maker's own product page or manual on 13 Nov 2026. Where makers give different figures, the page says so and uses the safer one.

Where the numbers come from

  1. Prince Pipes, SmartFit Plus CPVC product page: up to 82 °C, 25-year service life, SDR 11 fittings, heavy brass-insert MTA and FTA, yellow CPVC cement, jointing steps, pressure test after 24 h.
  2. Prince Pipes, Easyfit UPVC page: 5–60 °C, ½″ pipe 21.3 mm outside.
  3. Ashirvad, FlowGuard Plus CPVC page: up to 93 °C.
  4. A. O. Smith India, Elegance Slim Neo 15 L manual: 2,000 W, 25–75 °C, scald warning above 52 °C, 0.8 MPa highest inlet pressure, ½″ BSP connections, 6 in clearance (IS 302-1), multi-function safety valve on the cold inlet, may drip, never remove or block, lever to be operated regularly, non-return valve at least 40 ft away, braided hoses of 8 bar or more, blue inlet and red outlet stickers, Teflon clockwise, separate socket, no adaptors, reliable earthing.
  5. Havells, Instanio Prime 6 L page: 3,000 W, 13.04 A, 0.8 MPa, multi-function valve stops pressure rising past 8 bar.
  6. V-Guard, Classo+ house wire page: 2.5 sq mm, 18 A in conduit (two cables, single phase).
  7. Central Electricity Authority, (Measures relating to Safety and Electric Supply) Regulations, 2023, reg. 44: residual current device, not more than 30 mA in homes.
  8. ASTM D2846 (CPVC hot and cold water, CTS sizes): ½″ CTS is 15.9 mm outside. Standard figure. Water held per metre worked out from this size at SDR 11.

Send us a photo before the tiles go on

WhatsApp a photo of your open bathroom wall with the geyser point marked. We'll look at it with you: CPVC on the hot side, the right adaptors, the valve drain and the 16 A point.